泰州中学人才公寓给排水设计毕业论文
2020-07-08 21:47:20
摘 要
本工程位于宁海中学内,总建筑面积约12500平米,其中:地上建筑面积10500平米,地下2000平米,占地面积1250平米。该建筑为框架结构,地上十层,地下一层,首层高度4.5米,二—十层层高3.6米。地下一层为设备用房和车库,地上部分为公寓。
给水系统分区供水,从市政管网上接两根DN80的引入管,负一层至地上四层为市政管网直供,五至十层采用无负压变频供水设备加压供水。地下消防水池采用钢筋混凝土结构,置于地下室泵房边,有效容积545.9立方米,分为两格。建筑室内排水采用污、废水分流制,室外排水采用污废合流制,直接排入市政污水管。排水立管采用专用通气立管。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑外排水,选择重力半有压流系统,雨水经屋面雨水斗收集后排入雨水管。
根据规范,该建筑为二类高层建筑,室外消火栓用水量40L/s,室内消火栓用水量20L/s,火灾延续时间2h。消火栓充实水柱高度13m,水龙带长度25m,水枪喷嘴流量5.42L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。
本工程的自动喷水灭火系统分两区。该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量31.6L/s。报警阀设于地下室泵房内,各层均设水流指示器、信号阀和末端试水装置,其信号均送入消防控制中心进行处理。选用有效体积18立方米消防水箱贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,设于屋顶,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。
关键词:给水系统 排水系统 消火栓系统 自动喷水灭火系统 雨水系统 热水系统
Water supply and drainage engineering design of
talents apartment in Ninghai middle school
Abstract
The project is located in Ninghai middle school, with a total construction area of 12,500 square meters, including 10,500 square meters on the ground and 2,000 square meters underground, covering an area of 1,250 square meters.The building is a frame structure with 10 floors above and 1 floor under the ground. The first floor is 4.5 meters high and the second to tenth floors are 3.6 meters high. Underground layer of equipment room and garage, overground part is for apartment.
The water supply system is partitioned. Two DN80 inlet pipes are connected from the municipal pipe network. The first to the fourth floor above the ground are directly supplied by the municipal pipe network and the fifth to tenth floor are supplied with pressure-free frequency conversion water supply equipment. The underground fire pool is made of reinforced concrete and placed in the side of the pump room in the basement. The effective volume is 545.9 cubic meters, divided into two grids. Sewage and waste water diversion system is adopted for indoor drainage of buildings, and combined sewage and waste water drainage system is adopted for outdoor drainage, which is directly discharged into municipal sewage pipe. Drainage riser adopts special ventilation riser. The drainage in the basement is collected and discharged into the sump pit by the drainage ditch, and then to the inspection well by the submersible sewage pump. For drainage outside the building, a gravity semi-pressure flow system is selected. Rainwater is collected in the rainwater bucket and discharged into the rainwater pipe.
According to the regulations, this building is a second-class high-rise building, with 40L/s water consumption for outdoor fire hydrants, 20L/s water consumption for indoor fire hydrants and 2h fire duration. Hydrant filling water column height: 13m; hose length: 25m; nozzle flow: 5.42l /s; fire standing pipe diameter: DN100. A test hydrant is installed on the roof layer, and a button to start the fire pump at a distance is set in each indoor fire hydrant box.
The automatic sprinkler system of the project is divided into two zones. The building adopts the wet automatic sprinkler system, and the design flow of the sprinkler system is 31.6L/s. The alarm valve is located in the basement pump room. Water flow indicator, signal valve and terminal water test device are installed on each floor. The signal is sent to the fire control center for processing. Selects the effective volume of 18 cubic meters water tank storage fire early 10 min water automatic sprinkler system, indoor fire hydrant system in the roof. In the initial stage, the fire was supplied by the tank, and the fire in the later period was supplied by the fire-fighting pump and spray pump in the basement.
Key Words: water supply system drainage system hydrant system automatic sprinkler system rainwater system hot water system
目录
摘要 I
Abstract II
第一部分 设计说明
第一章 给水系统 1
1.1给水系统方案选择 1
1.1.1方案比较和选择 1
1.1.2方案选择依据 2
1.2给水系统组成 3
1.3给水管道的布置与敷设 3
第二章 消防系统 5
2.1室内消火栓系统 5
2.1.1室内消火栓系统的选择 5
2.1.2系统组成 6
2.1.3设备及构筑物 7
2.1.4消火栓的安装 7
2.2自动喷淋系统 7
2.2.1室内自动喷水灭火系统的选择 7
2.2.2系统组成 8
2.2.3喷头的选择与布置 8
2.2.4设备的选择 9
2.2.5喷淋系统的安装 9
第三章 热水系统 10
3.1热水系统选择 10
3.2热水系统组成 10
3.3设备及构筑物 10
3.4热水管道系统的布置与敷设 11
第四章 室内排水系统 12
4.1排水系统选择 12
4.2 排水系统的组成 12
4.3主要设备及构筑物 12
4.4排水管道安装要求 13
第五章 雨水系统 14
5.1雨水排水系统的选择 14
5.2雨水排水系统的组成 14
5.3雨水管道的敷设与布置 14
第二部分 设计计算
第一章 给水系统计算 15
1.1用水定额及用水量 15
1.2给水方式 16
1.3设计秒流量计算 16
1.3.1 设计计算依据 16
1.4给水系统水力计算 17
1.4.1低区直供系统水力计算 21
1.4.2高区增压供水系统水力计算 23
1.5水表的选择 24
1.5.1分户水表的选择 24
1.5.2 总水表的选择 25
1.6给水系统校核 26
1.6.1、低区直供水校核 26
1.7高区供水设备选型 26
1.7.1 高区所需供水压力 26
1.7.2 高区增压泵参数确定 27
1.7.3减压阀的设置 28
第二章 室内消火栓给水系统计算 29
2.1消防水池 29
2.2屋顶消防水箱 30
2.2.1水箱的容积 30
2.3消火栓保护半径 30
2.4消火栓布置间距 31
2.5消火栓的确定 31
2.6消火栓的水力计算 32
2.7水泵接合器选定 35
2.8消火栓减压计算 35
第三章 自动喷水灭火系统计算 37
3.1自动喷淋灭火系统的基本参数 37
3.2管道与报警阀布置 37
3.3喷头的选用与布置 37
3.4喷头的布置间距 37
3.5系统的设计流量 38
3.6水力计算(特性系数法) 38
3.6.1高区喷淋水力计算: 40
系统水力计算 43
3.6.2地下室喷淋水力计算: 43
3.7增压及贮水设备 46
3.7.1选泵: 46
3.7.2稳压设备: 46
3.8水泵接合器 47
3.9喷淋减压孔板计算 47
第四章 生活热水系统计算 49
4.1设计参数 49
4.2热水制备及供应方式 50
4.3集热系统设计计算 50
4.3.2热水箱容积 51
4.4热水供应系统设计计算 51
4.4.1热水配水管网水力计算 51
4.4.2 热水循环管网计算 55
4.4.3选泵 66
第五章 室内排水系统计算 69
5.1排水体制及排水方式 69
5.2排水系统水力计算 69
5.2.1排水横支管水力计算 69
5.3 排水立管水力计算 73
5.3.1 WL-1排水立管水力计算: 73
5.3.2 WL-2排水立管水力计算: 73
5.3.3转换排水立管计算 74
5.4集水坑及提升泵计算选型 75
5.4.1地下室汽车坡道集水坑计算 75
5.4.2消防电梯集水坑及提升泵计算选型 76
5.4.3水泵房集水坑及提升泵计算选型 76
5.4.4空调机房集水坑及提升泵计算选型 76
5.4.5楼梯口集水坑及提升泵计算选型 77
第六章 建筑雨水排水系统计算 78
6.1屋面雨水排水方式 78
6.2降雨强度 78
6.3汇水面积 78
6.4设计秒流量 79
相关图片展示:
课题毕业论文、开题报告、任务书、外文翻译、程序设计、图纸设计等资料可联系客服协助查找。