明基高层建筑给排水工程设计毕业论文
2020-07-09 20:36:02
摘 要
给水系统采取垂直分区并联给水的方式,从市政管网以DN300的管道接水进入建筑,其中负三层至地上六层由市政管网直供,七层至十六层由变频加压供水设备供水。建筑内排水采用污废合流制,室外也是污废合流制,直接排入市政污水管网,排水立管采用专用的通气立管,形成双管制排水系统,其中地上一层单独排水,二至十六层集中排水。雨水排水系统采用重力流系统,采用外排水体制,顶层屋面雨水经雨水立管排至一层屋面,再由一层屋面雨水斗收集经由雨水立管排入市政雨水管网。建筑内消防及喷淋在火灾前10min用水由屋面消防水箱提供,取有效容积为48m3,后期灭火用水由地下一层的消防水池提供,其有效容积为560m3,分为两格,。
根据查阅规范可知,本建筑属于一类高层民用建筑,耐火等级为一级,室外消火栓用水量40L/s,室内消火栓用水量20L/s,火灾延续时间2h。消火栓充实水柱高度12m,水龙带长度25m,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。根据查阅规范可知,本建筑地上部分为中危Ⅰ级,地下部分为中危Ⅱ级,整个喷淋系统分三个系统,地下一层至地下三层为一个系统,一至六层为一个系统,六至十六层为一个系统。该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量34.91L/s。报警阀设于地下室泵房内,各层均设水流指示器、信号阀和末端试水装置,其信号均送入消防控制中心进行处理。
关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统
Abstract
The water supply system adopts the way of vertical partition and parallel water supply, a DN300 pipe picked from the municipal pipe network transports water into the building, minus three to six floors for the direct supply of municipal pipe network, seven to sixteen layers with variable-frequency water supply equipment pressurized water. In the construction, the sewage and waste water is discharged with one system, the outside is the same, the sewage and waste water is discharged into municipal sewage pipe network directly. Toilet multi-established forms, special ventilation risers, some additional loop vent, informing a double tube drainage system. The ground floor takes a separate drainage system, and the second floor to sixteen floor have a drainage riser. Basement drainage flow sewer collection to sump, submersible sewage pump lifting flows into the inspection Chamber. The gravity flow system is used in rainwater drainage system , and the inner drainage system is adopted. The annex adopts a separate rainwater drainage system, rainwater is collected through the roof rainwater pipe and collected by the rainwater pipe to the municipal rainwater pipe network. The fire water tank on the roof provides the fire water of the fore fire control, the volume of the tank is 18cubic. The fire water pool in the B1 provides the water for controlling fire in the late stage of fire. The effective volume of the pool is 560 cubic, and it is divided into two grids.
According to the specifications, the building two high-rise construction,outdoor fire hydrant water 40L/s, indoor fire hydrant water 20L/s, fire life 2h. 12m fire hydrant full water column height, hose length 25m, fire the riser tube diameter DN100. Set up a test fire hydrants in roofing, each fire hydrant boxes are equipped with remote start button for fire pump. According to the specifications, the part above this building is middle risk level one and the underground part is middle risk level two, the whole sprinkler systems is divided into three parts, the minus floor to third floor is low region, the forth floor to tenth floor is high region. Wet automatic fire sprinkler system in the building, spraying system design flow 27.73L/s,the real flow is 34.91L/s. The alarm valve located on the pump room in the basement, the floors are located water flow indicator, test water device and signal the valve at the end, its signal is fed into the fire control core for processing.
Keyword: water-supply system、drainage system、hydrant system、automatic sprinkler system、rainwater system
目 录
设计说明书
第一章 给水系统
1.1给水系统组成
1.1.1 给水方式对比
1.1.2方案选择依据
1.2给水系统组成
1.3给水管道的布置与敷设
第二章 室内排水系统
2.1排水系统选择
2.2 排水系统的组成
2.3主要设备及构筑物
2.4排水管道安装要求
第三章 雨水系统
3.1雨水排水系统的选择
3.2雨水排水系统的组成
3.3雨水管道的敷设与布置
第四章 消防系统
4.1室内消火栓系统
4.1.1室内消火栓系统的选择
4.1.2系统组成
4.1.3设备及构筑物
4.1.4消火栓的安装
4.2自动喷淋系统
4.2.1室内自动喷水灭火系统的选择
4.2.2系统组成
4.2.3喷头的选择与布置
4.2.4设备及构筑物
4.2.5喷淋系统的安装
设计计算书
第一章 给水系统计算
1.1用水定额及用水量
1.2给水方式
1.3低位水池尺寸设计
1.4 生活给水系统水力计算 1
1.4.1设计秒流量的计算
1.4.2市政直供部分水力计算
1.4.3变频恒压供水设备部分水力计算
1.5水表的选择
1.5.1总水表的选择
1.5.2分水表的选择
1.6市政直供部分校核
1.7增压供水设备选型
1.7.1高区给水系统所需压力
1.7.2增压设备
1.7.3减压阀的设置
第二章 室内排水系统
2.1排水体制及排水方式
2.2排水系统水力计算
2.2.1排水横支管水力计算
2.2.2排水立管水力计算
2.2.3排水通气立管的选用
2.2.4排出管水力计算
2.3集水坑及提升泵计算选型
2.3.1地下室车库集水坑计算
2.3.2消防电梯集水坑及提升泵计算选型
2.3.3水泵房集水坑及提升泵计算选型
2.3.4汽车坡道集水坑及提升泵计算选型
第三章 建筑雨水排水系统
3.1屋面雨水排水方式
3.2降雨强度
3.3汇水面积
3.4设计秒流量 41
3.5雨水斗选用
3.6连接管选用
3.7立管选用
3.8排出管计算
第四章 室内消火栓给水系统的计算
4.1消防水池
4.1.1消防水池的设置
4.1.2体积计算
4.2屋顶消防水箱
4.3消火栓保护半径
4.4消火栓布置间距
4.5消火栓的确定
4.6消火栓的水力计算
4.7水泵接合器选定
4.8消火栓减压计算
第五章 自动喷水灭火系统
5.1自动喷淋灭火系统的基本数据
5.2管道与报警阀布置
5.3喷头的选用与布置
5.4系统的设计流量
5.5水力计算(特性系数法)
5.5.1 高区喷淋水力计算
5.5.3 系统水力计算
5.5.4 选泵
5.6 水泵接合器
参考文献
结语
谢辞
设计说明书
第一章 给水系统
1.1给水系统组成
1.1.1 给水方式对比
该建筑为高层建筑,为克服高层建筑同一给水系统,低层管道中静水压力过大的弊端,保证建筑供水的安全可靠性,高层建筑给水系统应采取竖向分区供水,且分区应充分利用室外给水管网的水压,以节省能量。
按照GB50015-2003《建筑给排水设计规范》(2009年版)规定:高层建筑生活给水系统应竖向分区,竖向分区应符合下列条件:
(1)各分区最低卫生器具配水点处的静水压不宜大于0.45MPa,特殊情况下不大于0.55MPa。